7. MODBUS
IMS01J02-E2
125
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
Status
[H-TIO- , H-CIO-A,
H-SIO-A]
RO C
The respective channel status is assigned to
each bit in the holding register.
bit 0: Alarm 1 status
bit 1: Alarm 2 status
bit 2: Burnout status
bit 3: Heater break alarm status
(
OR
operation of the H-TIO-
module and H-CT-A module.)
bit 4: Control loop break alarm (LBA)
status
bit 5: Temperature rise completion status
bit 6: Heat-side manipulated output status
bit 7 to 15: Unused
Bit data 0: OFF 1: ON
[Decimal number: 0 to 127]
For H-SIO-A module, only alarm 1 status
(bit 0), alarm 2 status (bit 1), heat-side
manipulated output status (bit 6) are
effective.
Temperature rise
completion status
[H-TIO- , H-CIO-A]
RO
U
0: Rise not complete
1: Rise completed
Error code
[H-PCP-J]
RO U
0: Operations normal
1: Backup data check error
2: RAM read/write error
3: System structure error
4: Internal communications error
5: A/D converter error
6: Adjustment data error
Continued on the next page.