7. MODBUS
IMS01J02-E2
150
Continued from the previous page.
Name
Attri-
bute
Struc-
ture
Data range
Factory
set value
AO output value monitor
[H-AO-A/B]
RO C Display scale range *
Data will be valid in manual mode.
AO output set value
[H-AO-A/B]
R/W C Display scale range *
Setting will be valid in manual mode.
0.0
AO function selection
[H-AO-A/B]
R/W C 0: Unused
1: Manual mode (outputs data given by the
AO output set value)
2: Temperature measured value (PV)
3: Set value monitor
4: Temperature deviation value (deviation
between the temperature measured value
and set value monitor)
5: Heat-side manipulated output value
6: Cool-side manipulated output value
7: AI measured value
8: TI measured value
9: Opening monitor
(2 to 9: Recorder output mode)
1
AO corresponding
channel setting
[H-AO-A/B]
R/W C 1 to 20 (TIO channel)
1 to 40 (AI and TI channel)
Setting will be valid in recorder output mode.
1
AO zooming high limit
[H-AO-A/B]
R/W C AO zooming low limit to 100.0 %
Setting will be valid in recorder output mode.
100.0
AO zooming low limit
[H-AO-A/B]
R/W C 0.0 % to AO zooming high limit
Setting will be valid in recorder output mode.
0.0
AO zero point correction
[H-AO-A/B]
R/W C
−
5.00 to
+
5.00 %
0.00
AO full scale correction
[H-AO-A/B]
R/W C
−
5.00 to
+
5.00 %
0.00
AO display scale high
[H-AO-A/B]
R/W
C
Span 10000 or less *
(Within
−
9999 to
+
10000)
100.0
AO display scale low
[H-AO-A/B]
R/W
C
Span 10000 or less *
(Within
−
9999 to
+
10000)
0.0
AO decimal point
position
[H-AO-A/B]
R/W C 0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
1
AO output change rate
limiter
[H-AO-A/B]
R/W
C
0.0 to 100.0 %/second (0.0: OFF)
0.0
* The position of the decimal point differs depending on AO decimal point position (P. 150) setting.
Continued on the next page.