6. RKC COMMUNICATION
IMS01J02-E2
106
Positioning adjustment counter
Item
Setting data
(Setting
counter
value)
Description Status
0
Normal
status
1
Opening adjustment star, open-side output start
(Motor time: 110 %)
2
Capture the open-side opening value after 3 seconds
stop
3
Close-side output start (Motor time: 110 %)
4
Capture the close-side opening value after 3 seconds
stop
Opening
adjustment
5
Above data stored in H-TIO-K module
Automatic
6
Hold
status
7
Outputs the close-side until the positioning becomes
0 %.
Open-side output start if the positioning is less than
0 %.
Stops at an positioning of more than 100 %, and
capture the motor time by H-TIO-K module
Capture the
motor time
8
After the motor time has been captured, close-side
output comes ON (Motor time : 110 %)
Automatic
9
Hold
status
−
10 to 100
Not settable
When you input setting counter 1, the opening adjustment starts, operations are carried out
automatically up to setting counter 6, then the system goes on hold status. When you input setting
counter 7, the motor time capture starts, operations are carried out automatically up to setting counter
9, then the system goes on hold status. After the settings are complete, always set to “0: Normal
status.”