7. MODBUS
IMS01J02-E2
122
Data whose decimal point’s presence and/or position depends on input
range
The position of the decimal point changes depending on the input range type because the Modbus
protocol does not recognize data with decimal points during communication.
The following data can have one of three decimal point positions:
No digit below decimal point, 1 digit below decimal point, 2 digits below decimal point
For details, see
Input range table (P. 107).
The input range for voltage/current input
(H-TIO-H/J module) and H-SIO-A module is fixed at 0.0 to 100.0 %.
Temperature measured value (PV)
Motor speed measured value (H-SIO-A)
Temperature set value (SV)
Motor speed set value (H-SIO-A)
Set value monitor
Alarm 1 set value
Alarm 2 set value
LBA deadband
Temperature rise completion range
Display scale high
(H-TIO-H/J, H-CIO-A, H-SIO-A)
Display scale low
(H-TIO-H/J, H-CIO-A, H-SIO-A)
H-SIO-A output scale high
H-SIO-A output scale low
H-SIO-A correction actual measured value
Setting limiter (high)
Setting limiter (low)
Example: When the temperature set value is -20.0
°
C, -20.00 is processed as -200,
-200 = 0000H - 00C8H = FF38H
Temperature set
High
FFH
value Low
38H
Input error determination point (high)
Input error determination point (low)
AT bias
Cascade monitor
AI measured value
AI alarm 1 set value
AI alarm 2 set value
AI display scale high
AI display scale low
TI measured value
TI alarm 1 set value
TI alarm 2 set value
AO output value monitor
AO output set value
AO display scale high
AO display scale low
Event DO extension alarm set value