background image

 

 

Installation instructions   

for authorized electricians 

 

sonnenProtect 1300-AU-IN-ATS 

 

KD-

AUD0420

 · Art.-Nr. 

130002

 · Version X01

                             

[email protected]   www.sonnen.com.au

 

 

Summary of Contents for SonnenProtect 1300-AU-IN-ATS

Page 1: ...Installation instructions for authorized electricians sonnenProtect 1300 AU IN ATS KD AUD0420 Art Nr 130002 Version X01 support sonnen com au www sonnen com au ...

Page 2: ...9 5 Mounting 9 5 1 Scope of Delivery 9 5 2 Selecting the installation location 10 5 2 1 Requirements for the installation location of the sub board 10 5 2 2 Observe minimum distances 10 6 Accessory installation 11 6 1 Installing the sonnenProtect 1300 AU IN ATS accessory 11 6 3 Connecting the cable and strands 12 6 3 1 Removing the dummy plug 12 6 3 2 Installing the cable gland 12 6 3 3 Wiring the...

Page 3: ...3 7 1 2 Switching on the grid voltage 16 7 2 Testing function 17 7 Troubleshooting 18 8 Decommissioning 19 9 1 2 Disposal 19 ...

Page 4: ...g of the sonnenBatterie and sonnenProtect 1300 AU IN ATS must be carried out by an accredited sonnen installer 1 2 Designations in this document The following designations are used in this document complete designation designation in this document sonnenBatterie eco 9 43 storage system sonnenProtect 1300 AU IN ATS sonnenProtect 1 3 Explanation of symbols Extremely dangerous situation leading to ce...

Page 5: ...e The output of the sonnenProtect must not be connected to the building mains Only connect electrical loads that do not exceed the nominal power in continuous operation and maximum power when switched on of the sonnenProtect 1300W Failure to comply with the conditions of the warranty and the information specified in this document invalidates any warranty claims 2 2 Qualified electricians Improper ...

Page 6: ...d the storage system must be wired in accordance with the product documentation installation manual All repairs on the sonnenProtect must be performed by authorised sonnen service technicians only 2 5 Operational voltage of the sonnenProtect The sonnenProtect is connected to live electrical parts which poses a risk of electrical shock The storage system inverter also contains capacitors which carr...

Page 7: ...ds Dimensions Dimensions H W D in mm 120 50 140 Weight in kg approx 0 65 kg Safety Protection Standard IEC 61009 1 AS NZ 61009 1 Protective functions Overcurrent Earth Leakage Degree of protection IP 30 as per sonnen eco 9 43 main unit Ambient conditions Ambient temperature range 40 C Storage temperature range 50 C Transport temperature rang 50 C Maximum relative humidity 90 non condensing Permiss...

Page 8: ...lator for sonnenBatterie AC grid supply 6 6A MCB Main isolator for backup circuits after the RCBO 3 3 Function The outlet cable of the sonnenProtect supplies electrical power both in grid and emergency operation The switchover time between grid and emergency operation is stated in the technical data In the event that the sonnenBatterie is turned off or has an unexpected issue the power supply to t...

Page 9: ...Protect 5 Mounting 5 1 Scope of Delivery Check the following scope of delivery to ensure it is complete No Designation 1 Pre assembled sonnenProtect 1300 AU IN ATS accessory 2 M20 cable gland 3 M20 cable gland nut 4 30mA RCBO 10A RCD for installer to connect to AC output 5 25A MCB Main isolator for sonnenBatterie AC grid supply 6 6A MCB Main isolator for backup circuits after the RCBO ...

Page 10: ...o allow the unit to be easily reached 5 2 2 Observe minimum distances Observe the minimum distances specified in Figure 6 between the device and the storage system and neighbouring objects Install the sonnenProtect at the same level as the top edge of the storage system if possible This keeps the cable lengths as short as possible The minimum distances ensure that The sonnenProtect sub board can b...

Page 11: ... switching on the device again Wait five minutes so the capacitors can discharge Check that the device is disconnected from the power supply Only authorized electricians accredited sonnen installers are permitted to carry out electrical work 6 1 Installing the sonnenProtect 1300 AU IN ATS accessory Install the sonnenProtect accessory on the mounting rail Use the free space to the left of relay K1 ...

Page 12: ...3 1 Removing the dummy plug Tools Screwdriver with a thin blade 0 4 mm Remove the dummy plug shown A screwdriver with a thin blade can be used for this purpose 6 3 2 Installing the cable gland Tools Spanner 25m Install the cable gland as shown ...

Page 13: ...ackup circuit is to be wired into a sub board If the accessory is not to be immediately connected then leave the output cable gland within the internal cavity of the main unit When wiring the output cable into a backup load switch board it is essential that the 30mA RCBO is used as the main switch and then in series the supplied 6A MCB is used to protect all sub load circuits against any excess dr...

Page 14: ...gement Insert the Active cable into the 5L3 connection along with the Black cable Connect the Neutral cable into the 3L2 connection along with the Grey cable Connect the Black cable into the L terminal connection of the T2 AC Power Supply and the Grey into the Neutral terminal connection To connect both cables insert a small flat screwdriver into the slots adjacent to each terminal input Connect t...

Page 15: ...appliances and or load circuits being supplied by the sonnenProtect do not exceed 6A 1300W All loads after the RCBO will need to be protected by the 6A MCB supplied with the sonnenProtect accessory set In some circumstances the combined power draw of both full charge rate of the sonnenBatterie 3300W as well as the full power supply of the sonnenProtect 1300W need to be considered To enable this si...

Page 16: ...ed on Do not attempt switching on the storage system more than three times Contact sonnen service Further attempts can damage the battery modules Fuse switch F1 establishes the connection between the battery and the inverter 1 Switch on fuse switch F1 The storage system then starts up and performs a self test Once the self test is successful the storage system is ready to operate 7 1 2 Switching o...

Page 17: ...in section 3 3 5 Press the test key of the RCBO to simulate an insulation fault of the sub board 6 Check whether the sonnenProtect is behaving as described for emergency operation in section 3 3 7 Ensure that the illuminated eclipse of the sonnen main unit has turned green whilst the unit is in backup mode If the sonnenProtect is behaving as described in section 3 3 the function test is successful...

Page 18: ...stem The RCD and or overall power from the sonnenBatterie is switching off immediately or after the sonnenProtect has been operating for a longer period An electrical consumer with a power consumption rating that is too high is connected to the output of the sonnenProtect Only connect loads with a power consumption that does not exceed the nominal power of the sonnenBatterie Only connect loads wit...

Page 19: ...tect it must be completely disconnected from the power supply 1 Switch off the RCD RCBO 2 Disconnect the storage system from the power supply 3 Wait at least five minutes until the capacitors inside the storage system inverter have discharged 4 Check that the voltage is no longer active 9 Uninstallation and disposal 9 1 Uninstallation Improper uninstallation of the sonnenProtect Danger to life due...

Page 20: ...20 www sonnen com au www sonnensupport com au ...

Reviews: