GTR058 Installation Manual:
Rev 22
21
P4: Primary/Secondary Closing Interval Setting.
Adjusting this value will change the time interval between the Primary Gate closing and the Secondary Gate
closing. By default, the Primary gate will begin closing 3 second before the secondary gate. If you would like both
your gates to begin closing simultaneously adjust this setting to 0 (seconds).
Default setting is ‘3’.
This value can be set between 0-9 seconds. Setting the value to ‘0’ means both gates will open simultaneously,
while setting the value to ‘9’ means that the Secondary Gate starts to open 9 seconds
after the Primary Gate.
Note: If you are fitting an electric lock to your swing gate. Please keep both P4 set to 3 seconds or longer.
P5: Stall Force of Gate Motor 1
The Stall Force setting adjusts the amount of resistance required to stop the motor. The value can be set
between 0-9. ‘1’ means minimum force detected will stop the gate, ‘9’ means the maximum force detected is
required to stop the gate. If an impact is detected during the opening cycle, the gate will stop. If an impact is
detected during the closing cycle the gate will stop, and then re-open.
For safety, this setting should be high enough that small objects such as branches or wind will not cause
interruptions, but low enough to detect collisions with a person or vehicle.
Default setting is ‘3’.
*NOTE* The Stall Force is an important part of the safety features. After any adjustments are made, this
function must be re-tested. Never increase the Stall Force to compensate for a gate that is dragging on
the ground, or that is too difficult to move manually (without motor force).
P6: Stall Force of Gate Motor 2.
As per above description for P5, the value can be set between 0-9. ‘1’ means minimum force detected will stop
the gate, ‘9’ means maximum force.
Default setting is ‘3’.
P7: Max Running Time of Gate Motor 1.
The Max Running Time can be set to stop the motor running after a set period of time.The value can be set
between 1 – 50 seconds. This is the maximum length of time the motor will try and open or close for.
The value can be set between 1 – 50 seconds. ‘1’ means the Gate Arm 1 will stop after 1 second.
Default setting is ‘40’ (seconds). There is no need to adjust this setting.
P8: Max Running Time of Gate Motor 2.
As per above description for P7
The value can be set between 1 – 50 seconds. ‘1’ means the Gate Arm 1 will stop after 1 second.
Default setting is ‘40’ (seconds). There is no need to adjust this setting.