Mounting
position
Description
G1
Normal mounting position
The air that is heated inside the component can flow
out of the component in a vertical upward direction.
Natural convection supports the forced cooling air cur‐
rent. This avoids the generation of pockets of heat in
the component.
1.
Mounting surface in control cabinet
2.
Outgoing heated air
3.
Component
4.
Fan inside the component (forces the cooling air
current)
5.
Cooling air
G2
180° to normal mounting position
G3
90° to normal mounting position
G4
Bottom mounting; mounting surface on bottom of control cabinet
G5
Top mounting; mounting surface at top of control cabinet
Tab.5-8:
Mounting Positions
Mounting Positions of Motor-Integrated Servo Drives
IM B5
IM V1
IM V3
Flange mounting on drive
side of flange
The drive electronics of a
motor-integrated servo
drive can be oriented as
desired.
Flange mounting on drive
side of flange, drive side
bottom
Flange mounting on drive
side of flange, drive side
top
Tab.5-9:
Allowed Types of Installation According to EN 60034-7:1993
Damage caused by penetration of fluids!
NOTICE
If fluid is present at the output shaft over a prolonged time in mounting posi‐
tion IM V3, the fluid may enter the housing and cause damage.
Ensure that fluid cannot be present at the output shaft.
5.3.3
Compatibility With Foreign Matters
All Rexroth controls and drives are developed and tested according to the
state-of-the-art technology.
DOK-INDRV*-SYSTEM*****-PR06-EN-P
Rexroth IndraDrive Drive Systems with HMV01/02 HMS01/02, HMD01, HCS02/03
Bosch Rexroth AG
63/309
General Data and Specifications