Without mains choke
With HNL Mains choke
With mains choke of higher in‐
ductance
1.7 x L
N
of HNL
I
L_cont
5%
50%
100%
5%
50%
100%
5%
50%
100%
k
f
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Ik/I1
Hz
%
%
%
%
%
%
%
%
%
THD
%
173,08
156,32
144,86
120,86
81,18
71,24
98,08
62,61
41,12
ki
0,87
0,84
0,82
0,77
0,63
0,58
0,70
0,53
0,38
k
k = 1: Fundamental wave; k ≥ 2: Harmonics number
I
L_cont
Maximum input current (mains input continuous current), see technical
data of device - Data for Mains Voltage Supply
ki
Distortion factor or harmonic content
I
k
Harmonic current of the k-th harmonic
I
1
rms value of the 1st harmonic (fundamental wave)
THD
Total Harmonic Distortion
Tab.18-6:
Harmonics HMV…E and HCS
Harmonics of Supply Units, Re‐
generative (HMV…R)
In the end application, the harmonics values are within the mini‐
mum and maximum values listed below. The harmonics values
depend on
●
Load distribution
●
Conditions in the mains
●
Mains pollution which other devices feed in the mains
If the degree of mains pollution generated by other devices is low,
the resulting values of the harmonics in the mains current of the
drive system are minimum values. If there is a high degree of
mains pollution generated by other devices, the maximum values
of the table can be reached in the worst case.
Ik/I1
k
f
Min.
Typ.
Max.
Hz
%
%
%
1
50
100%
100%
100%
2
100
2,5
4
25
3
150
2
5
25
4
200
2
3
25
5
250
2
17
35
6
300
2
2
30
7
350
1,6
7
30
8
400
1
2
12
9
450
1
2
10
10
500
1
2
8
11
550
1
5
12
Bosch Rexroth AG
DOK-INDRV*-SYSTEM*****-PR06-EN-P
Rexroth IndraDrive Drive Systems with HMV01/02 HMS01/02, HMD01, HCS02/03
292/309
Appendix