Property damage due to mains filter overload!
NOTICE
●
Do not connect mains filters in series, as this can cause resonance ef‐
fects on current and voltage.
●
Comply with the specified limits of C
y
(capacitances against housing),
maximum leakage capacitance C
ab_g
and maximum number of axes, be‐
cause otherwise the mains filter can lose its effect and get damaged.
●
Only operate expressly allowed components at mains filters.
Do not operate any other components, such as additional power supply
units and fans, at HNF mains filters.
With mains filters at compensation units, make sure there aren't any reso‐
nance effects on current and voltage.
Observe the allowed harmonic limit values (THD) of the filter components
(see
chapter 15.3.7 "Determining the Allowed Operating Data of Mains Fil‐
).
Make sure that the nominal current of the mains contactor does not exceed
the nominal current of the mains filter.
Circuit for the mains connection
Observe the chapter
9 Circuits for the Mains Connection,
.
Mains filters HNF01, NFD at mains grounded via outer conductor
HNF01.1 or NFD03.1 mains filters are not suited for operation on
mains grounded via outer conductor.
Observe the allowed mains connection voltage in the technical
data of the respective component.
Install an isolating transformer.
Performance data without mains choke
Operation without mains choke is only allowed for certain supply
units and converters.
Take into account that supply units and converters, when operat‐
ed without mains choke, have reduced performance data in com‐
parison to normal operation with mains choke.
Performance data: See technical data of the respective compo‐
nent