7.1. Faults Display
Code
Causes
Solutions
RTC
Clock Error
The device will not store date and time when
the HACCP alarm appears
Set the current date and time
CABINET
PROBE
Probe Error
The type of probe is incorrect.
The probe is defect.
The probe - electronic card connection is
incorrect.
The temperature detected by the probe is
beyond the limits allowed by the cell probe in
use.
Contact the after-sales
service.
Make sure the probe is of
kind PTC.
Verify the integrity of the cell
probe.
Verify the accuracy of the
connection instrument -
probe.
Check that the temperature near
the cell probe is not beyond the
established limits
EVAPORATOR
PROBE
NEEDLE
SENSOR 1
NEEDLE
SENSOR 2
NEEDLE
SENSOR 3
THERMAL
SWITCH
Evaporator Baffle Error
The evaporator fan baffle has been opened.
Contact the after-sales
service.
Close the evaporator fan baffle.
Compressor Thermal Alarm
The absorption of the compressor has
exceeded the allowed maximum
Contact the after-sales
service.
Air the room.
Clean the condenser.
Check that the fans are
working properly.
HIGH
PRESSURE
SWITCH
High Pressure Alarm
The pressure detected by the maximum
pressure switch is higher than the limit value.
Contact the after-sales
service.
Air the room.
Clean the condenser.
Check that the fans are
working properly.
LOW
PRESSURE
SWITCH
Low Pressure Alarm
The pressure detected by the minimum
pressure switch is lower than the limit value.
Contact the after-sales
service.
Ensure that the system
does not have a gas leak.
Check that the solenoid lock
valve opens while operating of
the compressor.
DOOR
OPEN
Door Open
The door is open. If the alarm persists, verify
the door micro switch alignment