26
| Grandview
®
G800EH Gas Fireplace
installation
Caution Requirements
The top, back and sides of the fireplace are defined by
standoffs. The metal ends of the standoff may
NOT
be
recessed into combustible construction.
WARNING
Fire hazard is an extreme risk
If these clearances (air space) to combustible materials are not adhered to. It
is of greatest importance that this fireplace and vent system be installed only in
accordance with these instructions.
Cool Wall Clearances
The clearances listed below are minimum distances unless otherwise stated.
A major cause of chimney related fires is failure to maintain required clearances (air space) to combustible materials. It is of the greatest
importance that this fireplace and vent system be installed only in accordance with these instructions.
Minimum Vent Clearances
to Combustibles
G800EH Clearance Requirements—Cool Wall Installations
Clearance:
Cool Wall - Clean Front
Measured From:
A: Mantel Height (min.)
**4" (102mm)
Top of Fireplace Opening
B: Sidewall
6" (152mm)
Side of Fireplace Opening
C: Ceiling
51-1/2" (1308mm)
Top of Fireplace Opening
D: Mantel Depth (max.)
18" (457mm)
Front of Fireplace Opening
E: Alcove Width
84" (2134mm)
Wall to Wall (Minimum)
F: Alcove Depth
36" (914mm)
Front to Back Wall (Maximum)
G: Convection Air Outlet
107" sq (690cm
2
)
Top/Front of Enclosure
H: Convection Air Outlet Opening
Ceiling Offset
Min. 2"
Top of Chase Vent Opening
K:
Chase Enclosure Ceiling (Min.)
*82" (2083mm)
From Base of Appliance Floor
L: Clearance to Sprinkler Head (Min.)
36" (914mm)
Perpendicular From Chase Grill
Notes:
0"
No Hearth Required
IMPORTANT - *A minimum of 107 square inches of open area. Chase enclosure ceiling must be flush with
ventilation opening required for all cool wall installations — this can be achieved by having an open area in
front. See manual for details.
** An extra 3/4" (19mm)of mantel height is required when using a faceplate.
Horizontal Top
2" (51mm)
Horizontal Side
1-1/2 " (38mm)
Horizontal Bottom
1-1/2" (38mm)
Vertical Vent
1-1/2" (38mm)
Alcove
E
F
H
A
B
C
D
E
F
G
K
Side view
L
Chase grill
Sprinkler
The
HeatWave
Duct Kit has different
clearance and framing requirements, check
the
HeatWave
manual for details.