Series 700/7000 Managed Industrial Ethernet Switch Hardware Manual - Volume II
2-55
Hardware Installation
Revised 2019-08-22
Mounting the Switch
Drawing No. LP0988
2.3.3
DIN
‐
Rail
Removal
Instructions
7900
Model
Remove the switch from standard 35mm DIN-Rail as shown in the diagram above.
1.
Ensure power from the power source is off.
2.
Disconnect power and ground wires.
3.
Disconnect any communications cables from the unit.
4.
Insert a standard flat/slotted screwdriver into the slot provided on the DIN-Rail clip.
5.
Using the base of the switch as a pivot point, apply upward force on the screwdriver to release the DIN-Rail
clip.
6.
With the DIN-Rail clip latching mechanism released, continue to rotate the switch upward and away from the
panel.
7.
Once the switch has been rotated upward, remove the screwdriver.
8.
Carefully lift the switch upward and away from the DIN-Rail and panel.
2.3.4
Rack
and
Panel
Mounting
Instructions
709FX,
710FX2,
711FX3,
712FX4,
714FX6,
7010TX,
7012FX2,
7506GX2,
and
7900
Models
Most of the switches are designed to be mounted on a standard 35mm Din-Rail. However, in the event that Din-
Rail mounting is not suitable for the application the optional Universal Rack Mount Kit (P/N: URMK) can be used to
mount the switch to standard 19” racks. Optional panel mounts are available if the application requires mounting
the switch to a panel or other flat surface. For the 709FX, 710FX2, 711FX3, 712FX4, 714FX6, 7010TX, and
7012FX2 models, the optional Panel Mount Assembly (P/N: CMPA-1 or CPMA-2) is factory installed.