Series 700/7000 Managed Industrial Ethernet Switch Hardware Manual - Volume II
2-71
Hardware Installation
Revised 2019-08-22
Fault Pins
Drawing No. LP0988
2.7
Fault
Pins
7026TX switches have Fault pins that can be used for an alarm contact. An alarm contact is normally open and the
relay closes when a fault condition occurs. These pins can be used to connect an external warning device such as
a light in order to provide an external alarm. The conditions for generating a fault condition (closing the relay) can
be configured through software. The Fault pins are located on the back and have a current carrying capacity of 1A
at 24VDC.
2.8
Configuration
Devices
The switches have a configuration device insertion point labeled as “NTCD”. This point is used to insert the
NTCD-128 configuration device for saving or restoring switch configuration parameters quickly without the need for
a computer or software. Each switch NTCD insertion point location is provided below:
The SD and USB connectors are for temporary connection only.
2.8.1
NTCD
‐
128
SD
Card
Configuration
Device
2.9
Cleaning
Clean only with a damp cloth. Excess moisture or harsh chemicals can cause damage to the unit.
Model
709FX
710FX2
711FX3
712FX4
714FX6
7010TX
7012FX2
7026TX
7506GX2
7900
Location
Back
Back
Back
Back
Back
Back
Back
Back
Front
Front
WARNING
:
SD and USB are for temporary connection. Do not use, connect, or
disconnect unless area is known to be non-hazardous. Connection or disconnection in
an explosive atmosphere could result in an explosion
.
AVERTISSEMENT
:
USB et SD sont de connexion temporaire.
Ne pas utiliser, de
connecter ou déconnecter sauf si la zone est connue pour être non dangereux.
Connexion ou la déconnexion dans une atmosphère explosive pourrait entraîner une
explosion
.
Ideal for saving or restoring switch
configuration parameters quickly without
the need for a computer or software.
One configuration device per switch is
recommended.