35
The following conditions are displayed only while there is a
demand for heat present.
Display
Condition
Flame Lost
Flame was not detected.
Water Sw Open
Water pressure switch open.
Vent Sw Open
Vent switch #1 open.
Hi Limit 1 Fault
High-Temp. limit 1 open. Press MODE
key to remove lockout.
Hi Limit 2 Fault
High-Temp. limit 2 open. Press MODE
key to remove lockout.
Cabinet Temp Lm
Cabinet Temp. limit open.
Air SW Open
Air pressure switch open.
Fan Lockout
3 air switch faults within same heat
demand cycle. Power must be cycled
to clear the fault.
Diff Sw Fault
Differential Pressure switch failed
open.
Ign Try Failure
Unit failed to ignite on first or second
try.
Ign 60 min Delay
Gas valve failed 3 times in single call-
for-heat. Unit is locked out for 60-min.
Ignition Lockout
When available, Single-try ignition
failed and Lockout. Power must be
cycled to clear the fault.
Flue Over Temp
Flue temperature was higher than
390°F (199°C). Power must be cycled
to clear the fault.
Remote Wire Err
While Remote mode is active, both
Spa and Pool inputs are energized.
Outlet Over Temp
Outlet Temp was higher than 180°F
(82.0°C).
Low Flow Fault
Low flow conditions are detected in the
heater. Possible scaling.
High Flow Fault
High flow conditions are detected in
the heater. Possible condensation.
Flue Low Temp
Flue temperature is below 175°F
(79.5°C). Warning: Possible
condensation.
Flue Extreme Low
Flue temperature is below 140°F (60
°C). Service required. Press MODE to
remove lockout.
Call Service
Fan Lockout, Ignition Lockout or Flue
Extreme Low Temperature occurred
3-times in 48-hours. Contact Service
support.
Table Q. Heater Status Messages - Demand for Heat
See Troubleshooting guides, on pages
48
and
49
for
diagnosis.
The following conditions are displayed in Pool, Spa and
Remote modes when there are active fault conditions.
Display
Condition
In Sensor Fault
Water Inlet thermistor temperatures
disagree by more than 3°F (1.5°C).
In Sensor Open
Water Inlet thermistor sensor failed
open. Below 6°F (-14°C).
In Sensor Short
Water Inlet thermistor sensor failed
short. Above 188°F (86.5°C).
Out Sensor Open
Water Outlet thermistor sensor failed
open. Below 6°F (-14°C).
Out Sensor Short
Water Outlet thermistor sensor failed
short. Above 188°F (86.5°C).
Flue Sensor Open
Flue temp sensor failed open. Above
464° F (240°C).
Flue Sensor Shrt
Flue temp sensor failed short. Below
7.5°F (-13.5°C).
Flow Sensor Fail
When equipped, Flow sensor
readings are out of range (0 to 100
GPM).
Flame w/o CFH
Board is sensing flame when gas
valve is commanded shut.
Gas Valve Fault
Gas valve is sensed to be ON when
commanded OFF. 60-min. soft
lockout.
Pump Ctl Fail
When equipped, Pump Control
is enabled but not responding to
commands.
WChem Brd Fail
When equipped, Chemistry board
is enabled but not responding to
commands.
Diff Sw Closed
Control is sensing Differential
pressure switch closed when Fan is
not commanded.
Diff Sw Open
Fan is commanded for 10-seconds
without differential switch closing.
Internal Fault or
EEPROM Fault
Memory fault. Reset setpoints or
replace board if fault does not clear.
Clock/Fireman Sw
Time clock/fireman switch circuit is
open.
Low Temp
Lockout
Water temperature is below 36°F
(2°C).
Low Voltage
Controller is receiving supply voltage
below 17 VAC.
Table P. Heater Status Messages - Active Faults
Summary of Contents for AVIA 264A
Page 67: ...67 2 H 1 R 1 H 7 S 2 C 3 C 5 S...
Page 68: ...68 1 F 2 F 2 G 1 M 4 M 5 M 6 M 7 M 8 M 10 M 6 G 3 G 4 G...
Page 69: ...69 1 B 2 B 2 F 1 P 3 P 2 P...
Page 70: ...70 1 V 2 V 3 V 11C 11 M OPTIONAL...
Page 71: ...71 14 H 15 H 4 H 12 M 7 H 9 H 7 C 8 C 12 H 13 H 16 H 11 H 10 H 10 C 9 C 8 H 6 H 5 H 3 H...
Page 146: ...67 2 H 1 R 1 H 7 S 2 C 3 C 5 S...
Page 147: ...68 1 F 2 F 2 G 1 M 4 M 5 M 6 M 7 M 8 M 10 M 6 G 3 G 4 G...
Page 148: ...69 1 B 2 B 2 F 1 P 3 P 2 P...
Page 149: ...70 1 V 2 V 3 V 11C 11 M OPTIONAL...
Page 150: ...71 14 H 15 H 4 H 12 M 7 H 9 H 7 C 8 C 12 H 13 H 16 H 11 H 10 H 10 C 9 C 8 H 6 H 5 H 3 H...