Printer example:
Date
Time
Door
User
Transaction
[0278]
12/06/95
13:34
1
Unauthorized Access
[0282]
12/06/95
13:35
1
MASTER
Local Alarm Accepted
[0285]
12/06/95
13:37
1
Alarm Cleared
Cable or Reader Tamper Alarm (Easikey 1000 Plus Only)
The EK1000 Plus only gives this alarm if the reader has been wired to detect this
condition.
This alarm gives exactly the same displays and sounds as an Unauthorized
Access condition. However, the printed report is different.
Printer example:
Date
Time
Door
User
Transaction
[0278]
12/06/95
13:34
1
Anti-tamper Alarm
[0282]
12/06/95
13:35
1
EDITOR - 1
Local Alarm Accepted
[0285]
12/06/95
13:37
1
Alarm Cleared
Alarm Relay Response (Easikey 1000 Plus Only)
This section describes response of the Alarm Relays when the system activates
an alarm condition.
A relay output is provided on each door channel with a Common, Normally Open,
and Normally Closed terminals. Both of these relays have the same function for
the corresponding door channel.
The Alarm Relay activates when the corresponding door channel receives an
Unauthorized Access or Cable/Reader Tamper alarm condition. The relay
deactivates when the Alarm Condition clears or when an Editor accepts the
alarm with the internal reader.
Example: Alarm Relate 1 activates for alarm conditions on reader/door channel 1
and Alarm Relay 2 activates for alarm conditions on reader/door channel 2. The
relays deactivate when an Editor accepts the alarm with the internal reader or the
door/cable tamper condition clears.
No relay response for Door Left Open:
The relays do not respond to a Door
Left Open condition.
Channel Interlock affects relays:
When you use Channel Interlock, alarm
conditions on both door channels activate Alarm Relay 1. The EK1000 does not
use Alarm Relay 2.