Programming the Door Data
When editing Door Data program entries, you will edit items for Lock Release
Time, Door Open Time, Door Time Profile, Door Options, Lock Mode, Free Exit,
RTE Report, and the Set/Reset features. These program items are described
here in detail.
Lock Release Time
This is the amount of time that the EK1000 operates the lock output. Usually you
will want to enable the lock output a sufficient amount of time to allow people to
open the door. You may need to set a longer time for older or disabled people.
When you using a EK1000 Plus with door monitoring, the EK1000 Plus door
controller clears any remaining lock release time as soon as the door contact
closes.
Door Open Time (Easikey 1000 Plus Systems Only)
This is the amount of time that the EK1000 Plus allows at the end of the Lock
Release Time before the controller activates a Door Left Open warning.
Installation of a door contact is required.
You must enter a value here if you are using door monitoring and/or reader
tamper detection. A value of 0 disables door and reader tamper monitoring.
Door Time Profile
Enter in a Time Profile, 1-8 if the door requires automatic unlocking and locking
of secured doors. Enter in a 0 if the door is to remain secured at all times,
requiring a valid key/card or request to exit to pass through the door.
Door Options
Three are four options that you can program. The controller's display shows each
as a vertical bar, full height when set, half height when not set. Door Option
program items are listed here:
1 Lock Mode
UNSET
Lock operates as fail-secure, power applied to unlock door.
SET
Lock operates as fail-safe, continuous power to keep door secure,
removed power to unlock.