74-07579-000-A 2/96
Page 18
© 1996 Radionics, Inc.
Programming the System
This section fully describes the logical programming sequence used for system
setup and use. This includes programming the Master and Sub Editors into the
system along with full database programming used for the system.
Applying Power
Once you have installed the EK1000 door controller, readers and Request to Exit
devices, and have connected the wiring to the electric locking devices, you are
now ready to apply power to the EK1000. Follow this procedure for the initial
start-up of the system.
1. Disconnect all reader, lock, and printer terminal blocks from the EK1000.
2. Connect the power supply to the corresponding terminals (AC or DC depending
on the power supply you install) to the EK1000. The screen may briefly display
8888 and EK1000 will beep four times. The display will then clear and if you
installed an AC power source, the Red power LED illuminates.
3. Connect the first reader.
4. If installed, operate the RTE for the first reader. If you did not install an RTE
device, use a short piece of wire to short RTE to -V at the terminal block. The
display should show
Op
and the green LED on the reader should illuminate.
5. Repeat for the second reader if used.
6. Now proceed to install the Master Editor Key/card.
Installing the Master Editor Key/Card
To install the Master Editor Key/Card:
1. Press and release the small Reset button,
SW1, located at the top left-hand corner of
the circuit board. The EK1000 will beep four
times. While it is beeping, press and release
the Reset button again. The display will
flash horizontal bars.
2. Present a key/card to the EK1000's internal
reader. This will become the Master Editor
Key/Card.
3. The EK1000 will beep and the display
alternates between
Clr
and
ALL?
. This
means "Do you want to initialize and clear the whole database?"
If this is an
existing installation, proceed to Item 4 now.
If this is a new door controller that no one has programmed, then the answer
should be "Yes". Press
VOID/5
followed by
SEL/SAVE
to initialize and clear the
database. The display clears and the EK1000 installs the Master Editor
Key/Card.
4. If this is an existing installation and you do not want to erase the database, then
just press
ESC
. Use this step if you are just replacing the Master Editor
Key/Card. The display clears and the EK1000 replaces the Master Editor
Key/Card.
Figure 11: Horizontal Bars
in the Display