Analog Signal Input
Verbatim Owner's Manual
B-9
Note
The scanning time required by the unit to check all analog readings against
established setpoints increases with the number analog channels. With 16
channels, the time can total on the order of one second, and this imposes a
limit on how fast the unit can detect analog setpoint violations. Normally, this
will not be noticed unless you set Alarm Trip Delays of less than two seconds,
and there is no effect on the trip delay for contact channels in any case.
Refer to the following section for recording the corresponding voice messages
other than the spoken numerical values.
B.1.7
Summary of Analog Programming Codes
Code
Description
Signal Type:
5 ZZ 7 N
Select input signal type. 0 is default for 4-20 ma
Scaling:
5 ZZ 1 X.XX or POINT
Low end signal value
5 ZZ 2 YYYY.YYYY
Corresponding low end spoken value
5 ZZ 3 X.XX or POINT
High end signal value
5 ZZ 4 YYYY.YYYY
Corresponding high end spoken value
Setpoints
:
5 ZZ 5 X.XX
Low alarm limit setpoint
5 ZZ 6 X.XX
High alarm limit setpoint
5 ZZ 5(6) -0
Disable low (high) setpoint
Disable Channel:
5 ZZ 0
Turn off (disable) channel ZZ
B.1.8
Recording Speech Messages for Analog Channels
This information supplements the basic information in the manual on recording
speech messages. Refer to that information before attempting to record any
speech messages.
For analog input channels
, the default message is “The present channel N
reading is ...”
For any analog inputs
, in place of the default messages you may plan to record
a preamble message of the general form “The total water flow in gallons is” or
“the main tank water level in feet is.”
Use program code 1 ZZ to record the analog preamble message.
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...