Analog Signal Input
B-6
Verbatim Owner's Manual
which will automatically accept the present moment signal value as the low
input signal value, rather than having to enter the value shown as X.XXXX
above. Then, enter:
5 ZZ 2 YYYY.YYYY ENTER
where YYYY.YYYY is the corresponding low-end physical value which
you observe in real-world terms.
At another time, when the signal or physical variable is toward the high end of
the scale, enter the following pair of codes:
5 ZZ 3 POINT ENTER
which accepts the present signal level as corresponding to the high-end physical
value which you enter as:
5 ZZ 4 YYYY.YYYY ENTER
Example:
It may already be known from your system’s specification that for channel 6, a
low-end signal of 4 milliamps corresponds to a desired spoken value of 34.5
feet of tank water level. In such a case, you would use the System
Specifications Method to enter:
K
for 4 milliamps
5 06 1 4 ENTER
K
for a spoken reading of 20.5
5 06 2 20.5 ENTER
K
for 20 milliamps
5 06 3 20 ENTER
K
for a spoken reading of 34.6
5 06 4 34.6 ENTER
Then, suppose with the system in operation, you observe that the tank level is
31.7 feet, but the Verbatim reports a value of 31.45 feet. The discrepancy will
most likely be due to a discrepancy of the sensor’s actual output versus the
theoretical system specification. Regardless, to correct for it, keeping in mind
that the signal is presently near the high end of the scale, you would use the
Real-World Method, entering:
K
To reference the present signal level
5 06 3 POINT ENTER
K
To recalibrate 31.7 as the corresponding spoken value
5 06 4 31.7 ENTER
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...