Analog Signal Input
Verbatim Owner's Manual
B-7
Continue the example, there might also be a discrepancy toward the low end of
the scale. Suppose on another day you observe a tank level of 22.5 feet but the
Verbatim report 2293 feet. Since this signal is at the low end of the range, you
would enter:
5 06 1 POINT ENTER
and
5 06 2 22.5 ENTER
Note:
These Real-World Method adjustments did not require you to measure any
actual signal levels!
From that time on, assuming that the sensor maintains its calibration and has a
linear output, the spoken value should track the actual value very closely. The
Verbatim itself is much more accurate and consistent than almost any sensor
available to connect to it. Note that the signal does not need to be exactly at the
end of its range (e.g. 4 ma or 20 ma) for these programming steps. However, in
general the wider the spread between the signal levels used, the better informed
the Verbatim will be to reflect the actual relationship between the sensor’s
output and the real value being measured.
Note:
While the unit reports with very high accuracy and resolution, you do not
need to enter your programming value to the same high degree of accuracy
unless you choose to.
For TS705 Temperature Sensor Inputs
Selecting signal type “2” (TS705 sensor) will automatically load scaling factors
as describe earlier. However, these automatically loaded scaling factors are not
adjustable. If you want to be able to do Real World calibration adjustments for
temperature sensor inputs, then instead of selecting sensor type “2”, select
sensor type “1” (0-1 VDC input) and enter scaling factors as follows:
5 ZZ 7 1 ENTER
(Selects signal type 1)
5 ZZ 1 .843 ENTER
5 ZZ 2 -19.8 ENTER
5 ZZ 3 .316 ENTER
5 ZZ 4 120.1 ENTER
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...