Advanced Programming
Verbatim Owner's Manual
6-13
u
To establish a non-zero starting value for the spoken reading, add the
desired starting spoken value after the 7 and before ENTER.
u
To establish a scale factor (so that a number of pulses will be translated
into a single spoken unit count), press:
5 ZZ 8 N ENTER
where N is the number of pulses corresponding to a single spoken unit
count. For example, if a pulse from a flow meter occurs for each 1/10
gallon of water flow, but the desired report is needs to be in thousands of
gallons, a value of 10,000 would be used for N. The unit uses the word
“percent” in speaking of the scale factor.
The spoken scaled value will “roll over” to zero upon reaching 4,294,967,294
(2
32
). Values above this should not be entered at the keyboard.
The default message for Totalizer channels is “Channel N Totalizer count is N.”
User-recorded messages are normally done in two segments. Use program code
1 ZZ to record a preamble message such as “The total water flow reading is”.
Use program code 2 ZZ to record an ending units-of-measure message such as
“thousand gallons”. During the report, the unit will insert the digits comprising
the actual scaled value. In this example, the resulting complete report would be
“The total water flow reading is (spoken value) thousand gallons”.
u
To establish a Totalizer alarm set-point, press:
5 ZZ 6 N ENTER.
When the scaled value reaches N, the unit will go into Unacknowledged Alarm
and begin dialing. After the initial alarm has occured, a new alarm will not
occur until the user has reset the criteria. You may program a value of zero for
N to cancel any previously programmed Totalizer alarm set-point for channel
ZZ.
u
To clear out all Totalizer readings to zero in one step, press:
9 3 5 6 ENTER.
6.2.6
Alarm Trip Delays
The Alarm Trip Delay is the length of time after a violation occurs before the
unit goes into Unacknowledged Alarm and begins dialing. The default value is
2 seconds for all inputs and 0.1 minute (6 seconds) for power failure. During
this time, if a status is read, the message will be the ALARM message, with the
extra word “alert” appended. If the violation is corrected before the Alarm Trip
Delay times out, no alarm or dialout will occur.
There are two ways to change this Alarm Trip Delay: global (common for all
channels except power failure) programming, and individual programming for
each channel and power failure.
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...