Analog Signal Input
B-4
Verbatim Owner's Manual
where m is the gain and b is the zero crossing point or Input (ma -> offset.
The gain may be calculated from: m=(y2-y1)/x2-x1)
where x1, y1 is one coordinate pair on the graph and x2, y2 is the other.
Therefore, when you have chosen to enter non-default coordinates you are in
fact setting the gain factor. This gain factor is taken along with the input signal
type you have chosen which will define both the gain and offset.
Notice that each of the two points requires two separate coordinate pieces of
information to define: the signal level and the corresponding water level. With
two such points defined, an entire line or linear equation is defined, so that
given any new signal level, we could use the graph to “look up” the
corresponding water level. In operation, the Verbatim autodialer measures the
signal level presented to it, and then calculates the corresponding physical
value, all based on the line or linear equation defined by your entry of the high
end and low end scaling information whether done by the System Specification
Method or the Real World Method.
B.1.5
Additional Perspective on Scaling Factors
Analog Math
It may be useful, in comprehending the process of establishing the scaling
factors, to visualize a graph which relates the water level in a tank to the input
from a 4-20 ma transducer. To establish the relationship on such a graph, it is
necessary to define two separate points, or coordinate pairs ideally at two
widely separated points on the graph. For such a linear relationship any point on
the “reading” (Y) may be calculated from the formula:
y = mx + b
0
4
8
12
16
20
50
10
Feet
mA
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...