Programming and Testing
3 - 4
Verbatim Owner's Manual
All contact inputs are initially set normally closed (i.e. they will alarm on Open
Circuit). This is the default setting and, therefore, any open circuits, including
any inputs left disconnected during installation, will appear as alarms until the
inputs are programmed.
K
To automatically program the inputs:
Make sure all inputs are in their normal (non-alarm) state. Then press:
5 0 0 ENTER
The Verbatim autodialer automatically examines all inputs and programs them
to alarm on the opposite input state from their present status. This code 500
does not affect any channels that have been programmed for Disabled Channels,
Status Only, Run Time Meter, or Pulse Totalizer function.
L
Exceptions
In most cases, no further programming of contact inputs is necessary.
However, the following configuration options are available:
◆
To set any input to be disabled and never be annunciated, press:
5 ZZ 0 ENTER
where ZZ is the 2 digit channel number you are programming. Be sure to
always use a leading 0 for channels 1 through 9 to keep the channel
number a two-digit entry.
◆
To set an individual contact input for normally closed operation (i.e. to
alarm on Open Circuit), press:
5 ZZ 1 ENTER
K
To set an individual contact input channel for normally open operation
(i.e. to alarm on Closed Circuit), press:
5 ZZ 2 ENTER
K
To set inputs to report status only, program each individual channel as
follows:
5 ZZ 3 ENTER
This setup never causes an alarm to dial out.
K
To set contact inputs for the run-time meter function, program each
channel as follows:
5 ZZ 4 ENTER
Summary of Contents for Verbatim
Page 1: ...Verbatim Owner s Manual Owner s Manual...
Page 14: ...Overview 1 4 Verbatim Owner s Manual...
Page 22: ...Installation 2 8 Verbatim Owner s Manual...
Page 24: ...Programming and Testing 3 2 Verbatim Owner s Manual Front Panel Keys and Indicators Diagram...
Page 34: ...Recording Voice Messages 4 6 Verbatim Owner s Manual...
Page 80: ...Using the Alarm Ready Schedule Feature 7 12 Verbatim Owner s Manual...
Page 82: ...Maintenance Testing and Battery Replacement 8 2 Verbatim Owner s Manual...
Page 94: ...Verbatim Series SFP Autodialer A 8 Verbatim Owner s Manual...
Page 104: ...Analog Signal Input B 10 Verbatim Owner s Manual...
Page 108: ...Analog Signal Input B 14 Verbatim Owner s Manual...
Page 114: ...Remote Supervisory Control Output C 6 Verbatim Owner s Manual...
Page 118: ...Printer Options D 4 Verbatim Owner s Manual...
Page 126: ...Data Acquisition Central Data Logging E 8 Verbatim Owner s Manual...
Page 155: ...Cabling Diagrams Verbatim Owner s Manual G 1 G Cabling Diagrams...
Page 156: ...Cabling Diagrams G 2 Verbatim Owner s Manual G 1 RACO VSER 01 Serial Cable Connection Diagram...
Page 166: ...Verbatim Floobydust H 4 Verbatim Owner s Manual DC Power Connection Diagram AJ1 JB8 MINI PLUG...
Page 174: ...Verbatim Floobydust H 12 Verbatim Owner s Manual Heater Thermostat Mounting and Wiring Diagram...
Page 188: ...Verbatim Floobydust H 26 Verbatim Owner s Manual Motherboard Component Diagram...
Page 189: ...Verbatim Floobydust Verbatim Owner s Manual H 27 Jumper Block Diagram...
Page 192: ...Verbatim Floobydust H 30 Verbatim Owner s Manual...
Page 200: ...Verbatim Autodialer Specifications I 8 Verbatim Owner s Manual...
Page 201: ...Worksheets Verbatim Owner s Manual J 1 J Worksheets...
Page 236: ...Glossary Glossary 8 Verbatim Owner s Manual...
Page 244: ...Verbatim Owner s Manual...