81
1: Frequency command(Hz(free))
2:Output current(%/A)
3:Inverter rated current (A)
4:Inverter load (%)
5:Output power (kW)
6:Stator frequency (Hz (free))
7:communication data display
8: Output speed
9: Communication counter
10: Normal communication counter
Note: When the power is on, the standard monitor mode displays the operation
frequency (default setting) in the format of "0.0". This format can be changed to any
other monitor display format by setting f610
.
NO.
Parameter Name
Setting Range
Default
f611
Panel running order clear selection
0~1
1
0: Clear
(
when standby terminal OFF
)
.
1: Keep
(
when standby terminal OFF
)
.
Note 1: When f611=0, Put OFF the standby terminal (see input function 1) will stop the
motor..
NO.
Parameter Name
Setting Range
Default
f612
Panel operation prohibition (f000)
0~1
0
0: Permitted
1: Prohibited
This parameter can prohibited/permitted set panel operation frequency(f000) by key
▲and ▼.
NO.
Parameter Name
Setting Range
Default
f613
Prohibition of panel operation (RUN/STOP
keys)
0~1
0
0: Permitted.
1: Prohibition
.