91
Note: PLC power off memory refers to the memory of the running stage, operation
frequency of PLC before power off.
NO.
Parameter Name
Setting Range
Default
f752
Simple PLC running time unit
selection
0~1
0
0: Seconds (s)
1: Minute (min)
NO.
Parameter Name
Setting Range
Default
f771
Reverse point dynamic frequency
0~1
0
0: Prohibit reverse point dynamic frequency, both forward and reverse point dynamic
frequency, point dynamic frequency according to F701, acceleration time of point
dynamic frequency is 0.1s (non adjustable), deceleration time according to F011.
1: 0.1~20.0: Enable reverse point dynamic frequency, when forward point dynamic, point
dynamic frequency according to F701, forward point dynamic acceleration and
deceleration time according to F518 and F519; When reverse point dynamic, point
dynamic frequency according to F771, reverse point dynamic acceleration and
deceleration time according to F520 and F521.
2.9 Communication function parameter group
NO.
Parameter Name
Setting Range
Default
f800
Modbus baud rate
0~1
1
0: 9600 bps.
1: 19200 bps.
2: 4800 bps.
3: 2400 bps.
4: 1200 bps.
Note: If change f800, you need to make power off, then make power on, it will be active.
NO.
Parameter Name
Setting Range
Default
f801
Modbus parity
0~2
1
0: NONE, datum format : < 8, N, 2 >.
1: EVEN, datum format :< 8, E, 2 >.