26
f106
Motor electronic thermal
protection level 1
varies by model
varies by model
Set the motor rated current specified on the nameplate of the motor to f106. This
parameter allows selection of the appropriate electronic thermal protection
characteristics according to the particular rating and characteristics of the motor.
Note: If f603=1, f106 displays in amperes/volts. If f603=0, f106 displays in % term. The
100% standard value is the rated output current indicated on the nameplate.
NO.
Parameter Name
Setting Range
Default
f107
stall prevention level 1
varies by model
varies by model
This parameter adjusts the output frequency by activating a current stall prevention
function against a current exceeding the f107 specified level.
Note 1: Do not set f107 under the rated motor no-load current. Otherwise the inverter will
determine that it is performing motor braking and increase the frequency applied
to the motor.
Note 2: If f603=1, f107 displays in amperes/volts. If f603=0, f107 displays in % term. The
100% standard value is the rated output current indicated on the nameplate.
Note 3: When inverter current is exceeding the f107 specified level:
Output frequency is adjusted current exceeding the f107 specified level.
Note 4:During an OC alarm status, (that is, when there is a current flow in excess of the
stall prevention level), the output frequency changes. At the same time, “---c” is
displayed flashing on and off.
NO.
Parameter Name
Setting Range
Default
f108
Base frequency 2
25.0~400.0 Hz
50.0
f109
Base frequency voltage 2
50~660 V
varies by model
f110
Motor electronic-thermal
protection level 2
varies by model
varies by model
f111
Stall prevention level 2
varies by model
varies by model
Setting method is the same as f101
、
f102
、
f106
、
f107.