147
NO.
Parameter
Name
Setting Range
default
WRT
User
setting
f409
Small current
detection current
hysteresis
1~20%
10
○
f410
Small current
detection time
0-255 s
0
○
f411
Over-torque
trip/alarm
selection
0
:
Alarm
1
:
trip
0
○
f412
Over-torque
detection level
0~250%
130
○
f413
Over-torque
detection level
hysteresis
0~100%
10
○
f414
Over-torque
detection time
0.0~10.0 s
0.5
○
f415
Overvoltage limit
operation
0: Enabled. speed.
1: Disabled
2: Enabled (Quick
deceleration).
3: Enabled (Dynamic
quick deceleration).
2
●
f416
Overvoltage limit
operation level
100-150%
130
●
f417
Undervoltage
trip/alarm
selection
0: Alarm only (detection
level below 60%)
1: Tripping (detection
level below 60%).
2: Alarm only (detection
level below 50%)
0
●
f418
Instantaneous
power failure
coast stop
selection
0: disabled
1: factory reserved
2: Coast stop.
0
●
f419
Forced fire-
speed control
function
0: Disabled.
1: Enabled.
0
○