56
0
:
Disable, when power on
,
Inverter will not supply to the motor even if the input
terminal (to which forward/reverse run function is assigned) is ON, Only open the
input terminal and re-close it will start the motor.
1
:
Enable. when power on
,
Inverter will supply to the motor on the detection of the
forward/reverse run terminal is ON.
NO.
Parameter Name
Setting Range
Default
f368
AO2 analog output signal type
0~1
1
1: current signal output
2: voltage signal output
NO.
Parameter Name
Setting Range
Default
f369
AO2 analog output function selection
0~16
0
f370
AO2 analog output proportion zoom
1~1280
Model setting
f371
AO2 analog output slope
0~1
1
f372
AO2 analog output bias
0~100%
0
Settings of F369 - F372 refer to AO1 parameters of F348
2.5 Fault protection parameter group
NO.
Parameter Name
Setting Range
Default
f400
Retry selection (Selecting the number of
times)
0~10
0
0: disabled
1~10 times.
This parameter resets the inverter automatically when the inverter gives an alarm. During
the retry mode, the motor speed search function operated automatically as required and
thus allows smooth motor restarting.
Protective operation detection relay signals (T1A-T1B-T1C or T2A-T2B-T2C terminal
signals) are not sent during use of the retry function.
To allow a signal to be sent to the protective action detection relay (TxA, B and C
terminals) even during the retry process, assign the output terminal function 36 or 37 to
f315.