97
0: Motor slowdown to a stop.
1: Motor keep running at the speed setting by f009.
NO.
Parameter Name
Setting Range
Default
f910
wake up delay
0~600.0s
0.0
frequency
(
Hz
)
0
Run
command
OFF
time
(
s
)
ON
f 0 0 9
f 9 1 0
Operation
frequency
Frequency
command
Figure 2.39 description of wake up from sleep mode
NO.
Parameter Name
Setting Range
Default
f911
Auto wake up level
0~100.0%
0.0
When feedback detected value is smaller than f911 setting, inverter wake up from sleep
mode.
NO.
Parameter Name
Setting Range
Default
f912
Auto sleep level
0~100%
0.0
When feedback detected value is bigger than f912 setting, inverter enter into sleep mode
and stop the motor.
NO.
Parameter Name
Setting Range
Default
f913
Upper limit of PID setting
0~100%
100
f914
Lower limit of PID setting
0~100%
0
f913 and
f914 set the upper and lower limit frequency that determines PID setting.
NO.
Parameter Name
Setting Range
Default
f915
auto-stop time limit for lower-limit
frequency operation
0~600.0
0.1
See f501. Note:
f915 and
f501 are the same parameter internally.