11
1.4.2 Remote control mode
Under remote control mode, the command source and frequency setting source of the
inverter are set through parameters f002 and f003 respectively. The command source
and frequency setting source can be combined in any way. For example, when f002= 1,
f003= 3, the control effect of the inveter is the same as under the local control mode.
Example 1: Two-wire control running
Figure 1.7 Example of wiring for two-wire control running
Table 1.3 Parameter configuration of two-wire control running
Code
Parameter
Setpoint
Setpoint
f002
Selection of run command
0
0
f003
Selection of frequency command selection
1
1
f300
AI1 input function (analog or logic
selection)
0
0
f301
L1 logic input function
2
62
f302
L2 logic input function
3
63
f303
L3 logic input function
10
10
f305
Logic input mode setting
0
0
f306
Logic input type selection
1
1
f309
Forced- effective Logic input function
selection
1
0
Code
Parameter
Setpoint
Setpoint
L
I 1
L I 2
0
V
AI 1
10 V
AI 2
T 1 A
T 1 C
T 1 B
AC
Drive
0 V
L I 3
L I 4
Fault reset
reverse
forward