98
NO.
Parameter Name
Setting Range
Default
f916
PID setting of keypad
0~100%
0
See f830.
Note: f916 and f830 are the same parameter internally.
2.11 Monitoring function parameter group
Table 2.12 Status monitor mode
NO.
Parameter Name
Description
u000
CPU1 Version
E.g:
, G-type, v= g; P-type, v= p
;
u001
Operation
frequency
Value is displayed in Hz/free unit. See f604.
u002
Direction of
rotation
Forward run,
Reverse run.
u003
frequency
command value
Value is displayed in Hz/free unit. See f604.
u004
load current
The inverter output current (%/A) is displayed.
u005
input voltage
(AC RMS)
The inverter input voltage (200V) is displayed.
u006
output voltage
(AC RMS)
The inverter output voltage command (200V) is
displayed.
u007
Input terminal
status indicated
u008
Output terminal
status indicated
u009
cumulative
operation time
(0.01=1 hour, 1.00=100 hours)
u010
Output speed
Displays the motor speed ( min-1) by calculating with
output frequency and pole numbers.
u011
Rated current
The rated current of the inverter (A) is displayed.
u012
Torque current
The torque current (%/A) is displayed.
NO.
Parameter
Name
Description
v
100
0
1