DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
24 70.0%
FPUMP STP SPEED6
G25.4.24
/ Stop
speed 6 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 6
set in G25.1.10.
YES
25 70.0%
FPUMP STP SPEED7
G25.4.25
/ Stop
speed 7 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 7
set in G25.1.11.
YES
26 70.0%
FPUMP STP SPEED8
G25.4.26
/ Stop
speed 8 for one
fixed pump
+0.0% to
+250%
+70.0%
It sets the speed below which the drive must remain for stopping a
fixed pump whenever the operating setpoint is the local setpoint 8
set in G25.1.12.
YES
27 PIDiSL%=0.0%
PID INVE SLEEP %
G25.4.27
/ Sleep
level in inverse
PID
0.0% to
100%
0.0%
Level below which, the drive will sleep when the PID of the
application is inverted (setting of G25.2.8 PID INVERT = Y). It is set
in % of drive setpoint.
YES
28 SLEEP?=Y
G25.4.28
/ To
enable sleep
mode
N
Y
Y
This parameter operates together with option ’31 SLEEP CONDIT’
of parameter G8.1.1. User can disable the sleep option of the drive
but a PLC receives the warning of fulfilled sleep conditions through
the output relay configured with option ‘31’ and stops the system.
See option ‘31’ in parameter G8.1.1.
OPT
FUNCTION
N=NO
Sleep mode disabled.
Y=YES
Sleep mode enabled.
YES
10.20.11.
Subgroup 25.5 – S25.5: Speed Bypass
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 BY SPon=+70.0%
BYPASS ON SPEED
G25.5.1
/ Speed
bypass at the
starting of fixed
pumps
+0.0% to
+250%
+70.0%
The drive speed will be forced to the value set in this parameter
during the time set in G25.5.2 to avoid over-pressure situations at
the starting of a fixed pump.
YES
2 BY T ON=10s
BYPASS ON DELAY
G25.5.2
/ Time of
speed bypass
after starting
fixed pumps
OFF=0 to
999s
10s
During the time set here, the drive speed will be forced to the value
set in G25.5.1 to avoid over-pressure situations at the starting of a
fixed pump.
YES
3 BY SPof=+90.0%
BYPASS OFF SPEED
G25.5.3
/ Speed
bypass at the
stopping of fixed
pumps
+0.0 to
+250%
+90.0%
The drive speed will be forced to the value set in this parameter
during the time set in G25.5.4 to avoid under-pressure situations at
the stopping of a fixed pump.
YES
4 BY T OFF=5s
BYPASS OFF DELAY
G25.5.4
/ Time of
speed bypass
after stopping
fixed pumps
OFF=0 to
999s
5s
During the time set here, the drive speed will be forced to the value
set in G25.5.3 to avoid under-pressure situations at the stopping of
a fixed pump.
YES