SDRIVE 700
POWER ELECTRONICS
70
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
11 PUMP OV=20.0A
PUMP OVERLOAD LV
G11.11
/ Pump
overload level
0.0 – 3200A
20.0A YES
12 PMovl FIL=OFF
PMP OVL FILTER
G11.12
/ Filter
for pump
overload
OFF=0,
1 to 5s
OFF YES
13 Povl DLY=OFF
PMP OVERLOAD DLY
G11.13
/ Trip
delay time
because of pump
overload
0 – 249s,
OFF=250
OFF
Overload protection is a combination of parameters G11.11, G11.12
and G11.13. Drive turns off its output generating a fault 'F57 PUMP
OVERLOA' when the output current of the drive is higher than the
current set in G11.11 for the time adjusted in parameter G11.13.
By means of parameter G11.12, we can adjust the value of low-
pass filter for the current reading to avoid oscillations.
YES
14 UNDERLOAD=N
G11.14
/ To
enable underload
protection
N
Y
N
It allows the possibility of protecting the pump from underload
status.
OPT
FUNCTION
N=NO Underload
protection disabled.
Y=YES Underload
protection enabled.
To protect the pump from underload status is necessary to follow
the next steps:
Set this parameter to ‘YES’.
Set an underload current value (in G11.15) below which the first
detection condition will be met.
Set an underload speed value (in G11.16) above which the second
detection condition will be met.
Set a delay time to activate underload protection (in G11.17), once
elapsed, last underload condition will be activated.
If three previous conditions are given, the drive will stop the pump to
protect it from underload status.
YES
15 ULD CUR=___A
UNDERLOAD CURREN
G11.15
/
Underload
current
(0.2 to
1.50)·In
∗
Setting of the underload current below which the first detection
condition to activate the protection is met. This parameter operates
together with parameters G11.16 and G11.17.
YES
16 ULD SPD=+100%
UNDERLOAD SPEED
G11.16
/
Underload speed
+0.0% to
+250%
+100%
Setting of the underload speed above which the second detection
condition to activate the protection is met. This parameter operates
together with parameters G11.15 and G11.17.
YES
17 ULD DELY=10s
UNDERLOAD DELAY
G11.17
/ Delay
time to activate
underload
protection
0 – 999s
10s
Setting of the delay time to activate the underload protection. The
drive will wait for this time before activating the protection and then
will stop. This parameter operates together with parameters G11.15
and G11.16.
YES
∗
This value depends on the drive size.