POWER ELECTRONICS
SDRIVE 700
DESCRIPTION OF PROGRAMMING PARAMETERS
51
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
5 DIGITL IN 1=06
G4.1.5
/ Multi-
function Digital
Input 1
configuration
00 – 69
06
6 DIGITL IN 2=00
G4.1.6
/ Multi-
function Digital
Input 2
configuration
00 – 69
00
7 DIGITL IN 3=00
G4.1.7
/ Multi-
function Digital
Input 3
configuration
00 – 69
00
8 DIGITL IN 4=00
G4.1.8
/ Multi-
function Digital
Input 4
configuration
00 – 69
00
9 DIGITL IN 5=00
G4.1.9
/ Multi-
function Digital
Input 5
configuration
00 – 69
00
It allows user to configure the digital inputs for individual use.
OPT
DESCRIPTION
FUNCTION
00
NO USE
Input is disabled.
01 START
‘Start’ command from a normally
open push button (NO). First, It is
necessary to configure another
input as a ‘Stop’ command from a
normally closed contact (NC).
02 STOP1
‘Stop’ command from a normally
closed push button. Stop mode is
adjusted in G7.1 STOP 1. (NC)
03
STOP2-
RESET
‘Stop’ command from a normally
closed pushbutton. Stop mode is
adjusted in G7.2 STOP 2. Activation
of the input in this mode also acts
as a ‘Reset’ signal. (NC)
04
STOP1-
RESET
‘Stop’ command from a normally
closed pushbutton. Stop mode is
adjusted in G7.1 STOP 1. Activation
of the input in this mode also acts a
‘Reset’ signal. (NC)
05 START/STOP
It allows start when closed and stop
when open (2 wires start / stop).
(NO)
06
START-
RST/STOP
It allows start when closed and stop
when open (2 wires start / stop).
Activation of this input also acts a
fault reset. (NO)
07
RESET
‘Reset’ signal by push button. (NC)
08
START +
INCH1
‘Start’ command and inch speed 1
when closed. Inch speed is
programmed in G15.1 INCH1. (NO)
09
START +
INCH2
‘Start’ command and inch speed 2
when closed. Inch speed is
programmed in G15.2 INCH2. (NO)
Note 1
.
10 INV
SPEED
It causes deceleration of the motor
until motor is stopped, and inverts
the rotation direction. (NO)
Note 2
.
11
RESERVE
Reserved for future use.
12
RESERVE
Reserved for future use.
13 INV
INCHS
It inverts the fixed speed reference
set in G15.1, G15.2 or G15.3. (NO)
Note 2.
14 ACC/DEC
2
It active acceleration and
deceleration ramps are enabled.
Alternative acceleration and
deceleration rates are programmed
in G5.3 and G5.4. (NO)
15
REFERENCE
2
It allows selection of the alternative
speed reference as programmed in
G3.2. (NO)
16
RESERVE
Reserved for future use.
17 CONTROL
2
It activates the alternative control
mode as programmed in G4.1.2.
(NO)
18
START/STP –
RST
Like the option 06, but ‘Reset’ signal
will be activated after the drive is
stopped. (NO)
19 STOP
(2)
‘Stop’ command from a normally
closed pushbutton. Stop mode is
adjusted in G7.2 STOP 2. (NC)
20
SPEED LIMIT
2
It will change to the alternative
speed limits as programmed in
G10.3 and G10.4. (NO).
Note
: See following page.
NO
1
If two inputs set to options '08
Î
START + INCH1' and '09
Î
START + INCH2' are activated at the same time the
combination of 'START + INCH3' programmed in G15.3 INCH3 is enabled.
2
Rotation inversion in 'G10.9 INVERSION ?=Y' must be enabled.