SDRIVE 700
POWER ELECTRONICS
88
DESCRIPTION OF PROGRAMMING PARAMETERS
10.20.10.
Subgroup 25.4 – S25.4: Stop Conditions
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 LP T SLP=20s
DRIVE SLEEP DELY
G25.4.1
/ Delay
Time before
activating sleep
mode
OFF=0,
1 – 999s
20s
This delay time is applicable to the following conditions: sleep
speed, No Flow input, flow measurement and sleep current. If either
of them is fulfilled, the time to activate the sleep mode will start
elapsing.
Note:
The SD700 is configured to go to sleep according to the
conditions of the installation as factory setting. Nevertheless, all of
the parameters values described below have been checked
according to each installation, to guarantee a correct functionality. If
you do not want the equipment goes in sleep mode, these
parameters must be checked and set for this purpose.
YES
2 40.0%
DRV SLEEP SPEED1
G25.4.2
/
Sleep speed for
local setpoint 1
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 1, below which the drive will go to
sleep whenever local setpoint 1 is selected. It is set in % of motor
speed.
YES
3 40.0%
DRV SLEEP SPEED2
G25.4.3
/
Sleep speed for
local setpoint 2
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 2, below which the drive will go to
sleep whenever local setpoint 2 is selected. It is set in % of motor
speed.
YES
4 40.0%
DRV SLEEP SPEED3
G25.4.4
/
Sleep speed for
local setpoint 3
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 3, below which the drive will go to
sleep whenever local setpoint 3 is selected. It is set in % of motor
speed.
YES
5 40.0%
DRV SLEEP SPEED4
G25.4.5
/
Sleep speed for
local setpoint 4
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 4, below which the drive will go to
sleep whenever local setpoint 4 is selected. It is set in % of motor
speed.
YES
6 40.0%
DRV SLEEP SPEED5
G25.4.6
/
Sleep speed for
local setpoint 5
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 5, below which the drive will go to
sleep whenever local setpoint 5 is selected. It is set in % of motor
speed.
YES
7 40.0%
DRV SLEEP SPEED6
G25.4.7
/
Sleep speed for
local setpoint 6
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 6, below which the drive will go to
sleep whenever local setpoint 6 is selected. It is set in % of motor
speed.
YES
8 40.0%
DRV SLEEP SPEED7
G25.4.8
/
Sleep speed for
local setpoint 7
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 7, below which the drive will go to
sleep whenever local setpoint 7 is selected. It is set in % of motor
speed.
YES
9 40.0%
DRV SLEEP SPEED8
G25.4.9
/
Sleep speed for
local setpoint 8
+0.0 to
+250%
+40.0%
It allows setting the sleep speed 8, below which the drive will go to
sleep whenever local setpoint 8 is selected. It is set in % of motor
speed.
YES
10 FLsw ENA=N
G25.4.10
/ To
enable the NO
FLOW input to
sleep the drive
N
Y
N
It allows enabling or disabling the NO FLOW input to sleep the
drive. It operates when the drive speed is below the speed set in
G25.6.17 NO FLO/FILL=0.0%, above which, the NO FLOW input
can only operate as protection (PAUSE, FAULT).
If it has been enabled, by closing this input (activation of the NO
FLOW input) and after elapsing the set delay time, the drive goes in
sleep mode.
YES
11 Fsl L=0.0l/s
FLOW SLEEP LEVEL
G25.4.11
/ Flow
level to sleep
the drive
OFF=0.0 to
3276units
0.0l/s
The flow will be monitored and when it is below the level set here,
sleep time will start elapsing. Once elapsed this time, the equipment
will go in sleep mode. So it allows setting the flow value or the flow
read through the pulse or analogue input, below which, a situation of
‘no demand’ will be detected. This situation will send to sleep the
drive. When this parameter is set to OFF, it will be disabled. The
source of flow reading is set in G25.10.1.
YES