SDRIVE 700
POWER ELECTRONICS
96
DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
6 FP ALTER MOD=0
G25.9.6
/
Alternation mode
of fixed pumps
0 – 2
0
It allows selecting the alternation mode of the fixed pumps.
OPT
DESCRIPTION
FUNCTION
0 LINEAR
The drive will always start the fixed
pumps by following the same
sequence 1, 2, 3 and will stop them
in the same way 1, 2, 3 (no
alternation).
1 CYCLE
The first pump to start will be the
next one to the last stopped pump.
2 DUTY
SHARE
The drive will try to make the
operation times of all available
pumps equal.
YES
7 JPon P=0.0Bar
JOCKEY ON PRESS
G25.9.7
/
Starting pressure
of Jockey pump
0.0 – 3276
Engineering
units
0.0Bar
It sets a pressure level below which, the Jockey pump will start.
During periods of very low demand (for example, tank filling process
or opening of a couple of taps) the Jockey pump will start to cover
this demand. This pump will only start if the drive is sleeping and
additionally there is some relay configured in Jockey Pump mode.
Consult configuration of the outputs for additional information.
YES
8 JPon DLY=20s
JOCKEY ON DELAY
G25.9.8
/ Start
delay time for
Jockey pump
0 to 6500s
20s
It allows setting a delay time for the starting of Jockey pump. This
time will start elapsing after the starting condition of this pump is
met, this is, when the pressure is below the level set in G25.9.7.
YES
9 JPof P=0.0Bar
JOCKEY OFF PRESS
G25.9.9
/
Stopping
pressure of
Jockey pump
0.0 – 3276
Engineering
units
0.0Bar
Setting of the level above which Jockey pump will stop. If the drive
pump starts, then the Jockey pump will stop automatically although
this stopping pressure is not reached.
YES
10 PRp BYP=300s
PRIM.PUM.BYP.DLY
G25.9.10
/
Bypass time for
Priming pump
0.1 – 6000s
300s
Once stopped the priming pump and started the drive, if the input
configured as Pressure Switch is opened during this time, the fault
‘F72 IN PRES SW’ will be produced.
Note
: The fault F72 is only produced if there is some relay
configured as ’30 PRIMING PUMP’ and some digital input
configured as ’69 PRESSUR SWITC’.
YES
11 PRp DLY=OFF
PRIM PUM FLTdly
G25.9.10
/ Trip
time of F72
during Priming
pump is
connected
OFF=0,
0.1 – 6000m
OFF
If the priming pump is connected and this time has elapsed from the
starting of the same one without detecting pressure in the pressure
switch, the fault ‘F72 IN PRES SW’ will be produced.
Note
: The fault F72 is only produced if there is some relay
configured as ’30 PRIMING PUMP’ and some digital input
configured as ’69 PRESSUR SWITC’.
YES
10.20.16.
Subgroup 25.10 – S25.10: Flow Limitation Algorithm
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 FLOW SEL=PULSE
G25.10.1
/ Flow
reading source
PULSE
AI1
AI2
PULSE
It selects the PID reference source of the instantaneous flow.
OPT
FUNCTION
PULSE
Pulses from a programmable digital input
AI1
Reference from Analogue Input 1
AI2
Reference from Analogue Input 2
YES
2 MAX FLOW=1000 l/s
MAX ALLOWED FLOW
G25.10.2
/
Maximum
allowed flow
0.0 – 3276
Engineering
units
1000 l/s
Setting of the maximum value of the allowed flow.
When the flow value is higher than the value set in (G25.10.2 +
G25.10.3), the flow control algorithm will be activated showing
‘FLOW’ as drive status.
At this point, the pump speed reference will start to decrease by
using the ramp set in G25.10.5. The speed reference will decrease
until the present flow is lower than the value set in G25.10.2 minus
the margin set in G25.10.3. In that moment, the speed will remain
constant until the present flow is lower than the flow set in G25.10.4.
From this moment on, the PID regulator will take up the control
again, and the drive will start to regulate normally.
Note:
Default units of measurement which are displayed depend on
the selected engineering units.
YES
3 0%
OFFSET MAX FLOW
G25.10.3
/ Offset
percentage over
maximum flow
+0% to
+250%
+0%
Setting of the offset margin over the maximum allowed flow to
activate the algorithm (measured as % of G25.10.2).
YES