DESCRIPTION OF PROGRAMMING PARAMETERS
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
10 DIGITL IN 6=17
G4.1.10
/ Multi-
function Digital
Input 6
configuration
00 – 69
17
Note
: Coming from the previous page.
OPT
DESCRIPTION
FUNCTION
21 DC
BRAKE
It activates or deactivates dynamic
brake unit. (NO)
22
START MODE
2
To select the alternative starting
mode (Ramp / Spin) (NO)
23
CURRENT
LIMI2
To select the alternative current
limit. (NO)
24
EXTERN
EMERGE
To generate the fault ‘F56
EMERGEN.STOP’. (NC)
50
PMP
START/STP
Automatic starting of the system.
(NO)
51
FLOW PULSE
Pulses input for the flowmeter. (NO)
52
FIX PUMP1
FLT
Auxiliary pump 1 fault. (NO).
53
FIX PUMP2
FLT
Auxiliary pump 2 fault. (NO).
54
FIX PUMP3
FLT
Auxiliary pump 3 fault. (NO).
55
FIX PUMP4
FLT
Auxiliary pump 4 fault. (NO).
56
FIX PUMP5
FLT
Auxiliary pump 5 fault. (NO).
57 MAN
PROTstart
Manual starting including those
protections enabled by the user.
(NO).
58
HI PRESS FLT
High Pressure trip. (NC).
59
LO WATER FLT No Water trip. (NC).
60
LO PRESS FLT
To detect a Low Pressure situation.
(NO).
61 FLOW
SWITCH
To connect an external flow switch
(open / closed). (NC).
62 IRRIGAT
TRIP
To detect an external fault from the
irrigation equipment. (NO).
63 SETPONT
PIN1
64 SETPONT
PIN2
65 SETPONT
PIN3
Configuration of the low, medium
and high bit respectively, for
multiple references selection,
according to the following table:
They are NO contact.
DIGITAL INPUTS
DI(z)
=65
DI(y)
=64
DI(x)
=63
PID
SETPOINT
0 0 0
G25.1.5
‘SETPT1’
0 0 X
G25.1.6
‘SETPT2’
0 X 0
G25.1.7
‘SETPT3’
0 X X
G25.1.8
‘SETPT4’
X 0 0
G25.1.9
‘SETPT5’
X 0 X
G25.1.10
‘SETPT6’
X X 0
G25.1.11
‘SETPT7’
X X X
G25.1.12
‘SETPT8’
66
MAN REF 2
To select the second source or the
alternative source for the speed
reference. (NO).
67
MAN OVR STAR
Manual starting without protections,
for testing starting. (NO).
69
PRESSUR
SWITC
Detection of the pressure existing in
the system to be used with the
Priming pump. (NO)
NO