POWER ELECTRONICS
SDRIVE 700
DESCRIPTION OF PROGRAMMING PARAMETERS
45
10.
DESCRIPTION OF PROGRAMMING
PARAMETERS
The different parameters of the SD700 are displayed in the alphanumeric LCD. These parameters are
organized in groups (G1 to G25). To access to the parameters or sub-groups which are in a lower level,
press the
∗
key. When you have accessed the desired parameter, this parameter will be shown as either
a numerical value or a list of possible options.
Figure 10.1 Detail of Programming Line.
See the information below for the whole parameter list and possible options of configuration.
10.1.
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 LOCK PARMTRS=0
G1.1
/ Parameter
lock
0 – 2
0
It allows user to lock SD700 parameters totally or partially. To lock
you have to introduce a password in G1.2.
OPC.
DESCRIPTION
FUNCTION
0
NO
Parameter lock is not active.
1 PARTIAL
LOCK
All of parameters are locked
except for G1.1, G1.2, G4.3 and
G6.2 (PID reference).
2 TOTAL
LOCK
Only G1.1 and G1.2 can be
modified.
NO
2 PASSWORD_=OFF G1.2
/ Access
password
OFF,
0000 – 9999
0
It allows user to introduce a password to lock parameters and avoid
unauthorized changes in the programming.
If in G1.1 'Parameter lock ', option '1 or 2' has been chosen, then
this parameter appears automatically.
Unlock: In G1.1 = 1 or 2 set to '0
Î
NO'.
2 PASSWORD_?OFF
will
be displayed.
YES