POWER ELECTRONICS
SDRIVE 700
DESCRIPTION OF PROGRAMMING PARAMETERS
61
Parameter
Name /
Description
Range
Default
value
Function
Set on
RUN
1 SEL RELAY 1=02
G8.1.1
/
Selection of
Relay 1 control
source
00 – 31
02
Note:
Coming from the previous page.
OPT
DESCRIPTION
FUNCTION
28 PUMP
CNTRL
Drive activates the relay to connect
the fixed pump. See G25.9.1 to
G25.9.3.
29
JOCKEY
PUMP
For those periods of low demand if
the drive is in sleeping mode. This
pump will stop when the pump of
the drive is connected or when the
demand disappears.
30
PRIMING
PUMP
To fill the suction pipe. This pump
will stop when the suction is filled
and then the drive pump will start.
31
SLEEP
CONDIT
The relay commutates if the
equipment has the sleep conditions
fulfilled or not. Once the equipment
is stopping, the relay commutates
again. This function operates
together with the parameter
G25.4.28 (see this parameter).
NO
2 T R1 ON=0.0s
R1 ACTIVAT DELAY
G8.1.2
/ ON
delay time for
Relay 1
0.0 – 999s
0.0s
Allows user to set a delay time before activating relay 1.
If during this ON delay time the activation condition disappears, the
relay will not be activated.
YES
3 T R1 OFF=0.0s
R1 DEACTIV DELAY
G8.1.3
/ OFF
delay time for
Relay 1
0.0 – 999s
0.0s
Allows user to set a delay time before deactivating relay 1.
If during this OFF delay time the deactivation condition disappears,
the relay will follow activated.
YES
4 INVERT REL1=N
G8.1.4
/ Relay 1
inversion
N
Y
N
It allows user to invert the logic of relay 1 functionality.
Relay 1 has one normally open contact (connection 26/27) and
another normally close contact (connection 27/28).
OPT
FUNCTION
N=NO No
inversion.
Y=YES
Inversion of relay logical function.
NO
5 SEL RELAY 2=03
G8.1.5
/
Selection of
Relay 2 control
source
00 – 31
03
Note:
See parameter function of G8.1.1.
NO
6 T R2 ON=0.0s
R2 ACTIVAT DELAY
G8.1.6
/ ON
delay time for
Relay 2
0.0 – 999s
0.0s
Allows user to set a delay time before activating relay 2.
If during this ON delay time the activation condition disappears, the
relay will not be activated.
YES
7 T R2 OFF=0.0s
R2 DEACTIV DELAY
G8.1.7
/ OFF
delay time for
Relay 2
0.0 – 999s
0.0s
Allows user to set a delay time before deactivating relay 2.
If during this OFF delay time the deactivation condition disappears,
the relay will follow activated.
YES
8 INVERT REL2=N
G8.1.8
/ Relay 2
inversion
N
Y
N
It allows user to invert the logic of relay 2 functionality.
Relay 2 has one normally open contact (connection 29/30) and
another normally close contact (connection 30/31).
OPT
FUNCTION
N=NO No
inversion.
Y=YES
Inversion of relay logical function.
NO
9 SEL RELAY 3=05
G8.1.9
/
Selection of
Relay 3 control
source
00 – 31
05
Note:
See parameter function of G8.1.1.
NO
10 T R3 ON=0.0s
R3 ACTIVAT DELAY
G8.1.10
/ ON
delay time for
Relay 3
0.0 – 999s
0.0s
Allows user to set a delay time before activating relay 3.
If during this ON delay time the activation condition disappears, the
relay will not be activated.
YES
11 T R3 OFF=0.0s
R3 DEACTIV DELAY
G8.1.11
/ OFF
delay time for
Relay 3
0.0 – 999s
0.0s
Allows user to set a delay time before deactivating relay 3.
If during this OFF delay time the deactivation condition disappears,
the relay will follow activated.
YES
12 INVERT REL3=N
G8.1.12
/ Relay
3 inversion
N
Y
N
It allows user to invert the logic of relay 3 functionality.
Relay 3 has one normally open contact (connection 32/33) and
another normally close contact (connection 33/34).
OPT
FUNCTION
N=NO No
inversion.
Y=YES
Inversion of relay logical function.
NO