COMMONLY USED CONFIGURATIONS
Parameter
Name / Description
Value
G4: Inputs – S4.1: Digital Inputs.
1 CNTROL MODE1=2
G4.1.1
/ Main Control Mode
2
Î
REMOTE (Drive control is done through control terminals).
4 DIGIT I MODE=1
G4.1.4
/ Digital Inputs configuration
selection
1
Î
ALL PROGRAMMABLE (all digital inputs can be individually
configured by the user).
5 DIGITL IN 1=05
G4.1.5
/ Multi-function Digital Input 1
configuration
05
Î
Start/Stop (Allows the start/stop command to be given by a
switch).
6 DIGITL IN 2=15
G4.1.6
/ Multi-function Digital Input 2
configuration
15
Î
Reference 2 (It allows selecting the alternative speed
reference programmed in G3.2.)
12.2.2.
Connections drawing
Terminals 1 and 2: start / stop command (NO status).
Terminals 1 and 3: alternative reference command (NO status).
Figure 12.1 Start / Stop commands by terminals and speed reference by analogue input
Note:
Use screened cables for the controls and connect screen to ground.