SDRIVE 700
POWER ELECTRONICS
44
VISUALIZATION AND STATUS PARAMETERS. GROUP G0
Screen
Units
Description
ESTATUS PUMP
PROGRAM
-
In the visualization lines of the display, it is possible to select this option. In this way the
following messages are going to be shown according to the current program status:
Status
Description
PID REGULATION
Drive is regulating in PID mode.
PROTECTED MANUAL
The drive is at protected manual mode.
OVERRIDE MANUAL
Drive is in manual mode, not protective mode.
HI PRESSURE PAUS
Drive is stopped (pause) due to high pressure,
according to the read data in the analogue input.
HI PRESSURE FAUL
A fault due to high pressure has occurred according to
the read data in the analogue input or in the digital input.
NO FLOW PAUSE
The drive has stopped (Pause status) due to No Flow
detection.
NO FLOW FAULT
The drive has tripped (Fault status) due to No Flow
detection.
CAVITATION PAUSE
The drive has stopped (Pause status) due to Cavitation.
CAVITATION FAULT
The drive has tripped (Fault status) due to Cavitation.
LO PRESSURE FAUL
The drive has tripped due to low pressure fault.
LO WATER FAULT
The drive has tripped due to a fault detected in one of
the digital inputs configured as ‘No Water’
CYCLING FAULT
The drive has tripped due to excessive starting cycles.
IRRIGATOR FAULT
The drive has tripped due to a fault in the irrigation
equipment which has been detected in the digital input
configured in that option.
LIMITING FAULT
The drive is limiting the speed to limit the flow.
PUMP STOP
The drive has received the stop command.
SLEPT NO DEMAND
The drive is in sleep mode because there is no flow
demand.
BYPASSING SPEED
The drive is forcing the speed after starting or stopping
some of the fixed pumps.
SETPOINT RAMP
Set point ramp activated.
PIPE FILLING
The drive is running at reduced speed because Pipe Fill
function is active.
COMPLETED
The time of automatic stop has expired and the drive is
stopped.
JOCKEY PUMP ON
The Jockey pump is running.
PRIMING PUMP ON
The Priming pump (suction filling) is connected.
PRESSU SWITCH ON
The pressure switch is open.