Configuration of
induction loop 2
with DIP switch
S500
DIP 4
DIP 5
Opening loop
ON
ON
(Starts opening operation)
Safety loop
ON
OFF
(Stops closing operation)
Closing loop
OFF
ON
(Starts closing operation)
Loop deactivated
OFF
OFF
Use DIP switch
S501
to set the time after which the barrier is automatically closed, once a
vehicle has passed the closing loop.
DIP 1
Auto-closing after 3 s
ON
Auto-closing after 1.0 s
OFF
6.2.2.2.3 Setting the automatic reversing function
If a closing operation is stopped by a photoelectric barrier or an induction loop, automatic
reopening of the barrier boom can be set to occur after a preset time. This reversing action
can be set on DIP switch
S500
.
DIP 1
Reversing action ON
ON
Reversing action OFF
OFF
DIP 8
Automatic reversing after 1.5 s
ON
Automatic reversing after 0.7 s
OFF