Hand-operated boom barriers Type GHS
Electrically operated boom barriers Type GES
Electro-hydraulically operated boom barrier Type GEHS
P
erimeter
P
rotection
G
ermany
G
mbH
Document: 2050274
Created: 11.04.2011
Version: a
Changed: 15.08.2013
Page 55 of 93
Original version
Subject to change
Loop 1/ Loop 2 Loop 1/ Loop 2
DIP 1 / DIP 5
DIP 2 / DIP 6
Low sensitivity
OFF
OFF
Medium sensitivity
ON
OFF
High sensitivity
OFF
ON
Highest sensitivity
ON
ON
Setting the hold time
You can set the hold time for each loop separately.
Loop 1/ Loop 2
DIP 3 / DIP 7
Hold time: infinite
ON
Hold time: 5 minutes
OFF
LED indicators
Each loop-detector PCB has one green and one red LED which let you know the state of the
loop detector.
Green LED Red LED
No supply voltage
OFF
OFF
Calibration or frequency output
FLASHES
OFF
Detector ready, loop is free
ON
OFF
Detector ready, loop is engaged
ON
ON
Loop malfunction
OFF
ON
Note
If you switch the power supply back on, each detector is automatically
recalibrated. This process takes approx. 3 - 4 seconds. During this time, no
OPEN or CLOSE commands will be executed.