Delay Cancel Feature
For convenience, on a one time basis, the DELAY CANCEL feature will cancel the following safety
delays which can be set up in the IntelliTouch system. Please note there is generally not a need to cancel
any of these delays except for servicing or testing the system.
• Heater Cool-Down Delay Cancel:
Shuts Filter Pump off immediately.
• 2-Speed Filter Pump 5 minute START on HIGH SPEED Delay Cancel:
Shifts pump to low speed.
• Automatic Pool Cleaner START Delay:
Starts Cleaner Pump immediately. Normally there is a delay
in which the filter pump first runs for 5 minutes before the cleaner pump starts.
• Automatic Pool Cleaner-SOLAR Delay:
Allows Cleaner Pump to run even though solar delay has
shut it off for 5 minutes.
About the Heater Cool-down Cycle and Delay Cancel
Some heaters require a cool-down cycle before being turned off. This can be accomplished with a
SET UP procedure in the IntelliTouch system which runs the filter pump an additional ten minutes to
dissipate residual heat built up inside the heater combustion chamber. The DELAY CANCEL feature is
mainly for use by service technicians when they want to shut the filter pump off immediately, and know
the heater has not been running.
IMPORTANT:
Heaters manufactured by Pentair Water Pool
and Spa
®
do not require this cool-down period and do not need
the delay to be set up.
To cancel a safety delay:
Go to Delay Cancel Screen
1. Press the button next to
DELAY CANCEL
. Equipment is
switched off and ready to be serviced.
MENU DELAY CANCEL
Getting There
Master Spa/Pool (Heater Cool-Down) and Delays For Valves
(Continued)
Go to the
Pump Delays
screen.
1. Press the button next to
Master Spa/Pool
. Press the left or
right side button change the setting to
Yes
.
Note: Pentair
Water Pool and Spa
®
heaters do not require this feature.
2. Press the button next to
Delay For Valves
. Press the left or
right side button change the setting to
Yes
.
3. Press the
Save
button.
4. Press the
Exit
button to return to the main screen.
MENU/SETUP/EQUIPMENT/PUMP DELAYS
YES
DELAY FOR VALVES
YES
MENU SETUP
PUMP DELAYS
EQUIPMENT
Getting There