Table 18: Binary input setup screens descriptions, values, and selections
Screen name
Description
Value or
selection
To set an action mode for BI1, press
SET
.
n/a
ACTION
Conditional
screen
To set an action mode for BI1, select
NOR-MAL
,
FAN-OFF
,
COO-OFF
(cool off), or
AUX-ON
(auxiliary on), and press
SET
.
Note: ACTION
is not available for refrigerant leak mode.
If you select refrigerant leak mode for a binary input,
the mandatory action for that binary input is system
shutdown.
Door open:
•
NOR-MAL
•
FAN-OFF
•
COO-OFF
•
AUX-ON
To select an action delay time for BI1, press
SET
.
n/a
ACTION DELAY
Conditional
screen
Select an action delay value from the range 0 min to 10 min
and press
SET
.
0 min to 10 min
BI 2
This screen is the
BI 2
setup start screen. To go to the BI2
terminal setup screens, press
SET
.
n/a
MR5 Series Panel Mount Case Controller Technical Bulletin
42