Figure 27: ADPT EOL connection
Table 28: ADPT EOL connection
Callout
Description
1
Non-EOL device
2
EOL device: Connect the 220 0hm resistor to + and -
3
Master device - EOL switch off
Setting a new device address
About this task:
Set a new device address to connect the adapter to the controller. The default BACnet device
address is "07" and the default device ID is "1". To edit these values on the navigation screens,
complete the following steps:
1. On the
HOME
screen, press and hold
MENU/ESC
for 2 seconds to go to the
STATUS
start
screen.
2. Press
DOWN
to go to the
SYSTEM SETUP
start screen, and press
SET
.
3. Press
DOWN
to go to the
BACNET
start screen and press
SET
.
4. On the
DEVICE ADDRESS
screen, press
SET
to set a new device address.
BACnet objects available on the MR5 controller
The following BACnet objects are available on the controller.
Note:
Sensor 1 : Temperature is the only available BACnet object that supports trend.
MR5 Series Panel Mount Case Controller Technical Bulletin
60