Table 11: System component screen descriptions, values, and selections
Screen name
Description
Value or
selection
To set the measurement mode for SN3, press
SET
.
n/a
SN3:
MEASUREMENT
Conditional screen Select a value for the SN3 measurement mode. To save the
selection, press
SET
.
•
NON
•
DEF
•
CASE
To set the temperature averaging weight for SN3, press
SET
.
n/a
SN3: WEIGHT
Conditional screen
Select a weight value for SN3. To save the selection, press
SET
.
10% to 90%
To define the fan/aux relay, press
SET
.
n/a
RELAY: FAN/AUX
Select a definition for the fan/aux relay. To save the
selection, press
SET
.
•
FAN
•
AUX
To change the defrost type, press
SET
.
DEFROST TYPE
Select resistive electric heat, passive off-cycle, or hot gas
bypass defrost type. To save the selection, press
SET
.
•
ELC-TRC
•
OFF-CYC
•
HOT-GAS
To change the defrost termination type, press
SET
.
DEFROST TERM
TYPE
Conditional screen Select time-based defrost termination, or temperature-
based defrost termination (SN2). To save the selection,
press
SET
.
Note:
The
DEFROST TERM TYPE
screen does not display
when the defrost termination type is
OFF-CYC
because
off-cycle defrost termination is time-based.
•
TI-ME
•
TE-MP
QREV/PSHC
See
.
To change the MSTP connectivity selection, press
SET
.
n/a
MSTP
CONNECTIVITY
Select BACnet or Verasys connectivity. To save the selection,
press
SET
.
•
BAC-NET
•
VER-SYS
BACNET
To enter the BACnet menu, press
SET
.
n/a
To set a device address, press
SET
.
n/a
DEVICE ADDRESS
Select an address value between 4 and 127. To save the
device address, press
SET
.
4 to 127
To set a device ID, press
SET
.
n/a
DEVICE ID
Select a device ID value between 1 and 9999. To save the
device ID, press
SET
.
1 to 9999
MR5 Series Panel Mount Case Controller Technical Bulletin
30