Table 14: Refrigeration setup screen descriptions, values, and selections
Screen name
Description
Value or
selection
To set the failure mode for the case sensor, press
SET
.
n/a
CASE SENSOR:
FAILURE MODE
Select
ON
,
OFF
, or
AVG
and press
SET
. See
more information.
•
ON
•
OFF
•
AVG
To set the ASD time for the compressor, press
SET
.
n/a
ANTI-SHORT
CYCLE DELAY
Select the delay time value from the range 0 min to 12 min
and press
SET
.
0 min to 12 min
To set the state of the evaporator fan relay when the
compressor relay is off, press
SET
.
n/a
EVAP FAN:
COMPRESSOR
OFF
Conditional
screen
Select
ON
or
OFF
, and press
SET
.
•
ON
•
OFF
MR5 Series Panel Mount Case Controller Technical Bulletin
34