Table 15: Defrost cycle setup screens descriptions, values, and selections
Screen name
Description
Value or
selection
To set the evaporator fan delay time, press
SET
.
n/a
EVAP FAN
DELAY TIME
Conditional
screen
Select the delay time value from the range 0 min to 15 min
and press
SET
.
Note:
The evaporator fan delay time is the number of
minutes that the evaporator fans waits before turning on
after the compressor relay closes, post defrost duration
and driptime delay.
0 min to 15 min
To set the defrost schedule type, press
SET
.
n/a
DEFROST
SCHEDULE TYPE
Conditional
screen
To set the defrost schedule type, select
SCH-EDU
(scheduled)
or
ADA-PTI
(adaptive) and press
SET
.
Note:
The defrost schedule type screen appears only if
you select
TE-MP
on the defrost termination type screens,
under
SYSTEM SETUP
.
•
SCH-EDU
•
ADA-PTI
MR5 Series Panel Mount Case Controller Technical Bulletin