Note:
• Some of the following alarms are available only when the controller uses the corresponding
binary input or feature. For example, the QREV and PSHC alarms are available only after you
pair the MR5 controller with a QREV and PSHC.
• To make the door open and refrigerant leak optional alarms available and configurable on
the alarm setup screens, select the optional alarm type on the binary input setup screens.
Table 23: List of alarms and alarm true conditions
Alarms
Alarm TRUE Condition
The SN1 temperature is greater than the high temperature alarm threshold
value that you defined for a period of time equal to or greater than the alarm
delay.
High
Temperature
The SN3 temperature is greater than the high temperature alarm threshold
value that you defined for a period of time equal to or greater than the alarm
delay.
The SN1 temperature is less than the low temperature alarm threshold value
that you defined for a period of time equal to or greater than the alarm delay.
Low
Temperature
The SN3 temperature is less than the low temperature alarm threshold value
that you defined for a period of time equal to or greater than the alarm delay.
SN1 is in a state of failure.
SN2 is in a state of failure.
Sensor Failure
SN3 is in a state of failure.
PSHC Comm
Loss
Communication is lost with the PSHC.
PSHC Status
The PSHC status triggers an alarm.
Door Open
The door switch indicates that the door is open for a period of time equal to
or greater than the alarm delay. A different manufacturer can supply the door
switch.
Refrigerant
Leak
The refrigerant leak detector indicates a leak. A different manufacturer can
supply the leak detector.
Alarm actions
• Alarm Relay: The alarm relay energizes when any alarm condition is true. The alarm relay de-
energizes when you acknowledge the alarm locally or when the condition is no longer true.
• Local UI: The
Alarm
icon on the UI illuminates when any alarm condition is true or requires
acknowledgment.
Alarm settings
The following table provides information about the alarm parameters and their corresponding
descriptions:
53
MR5 Series Panel Mount Case Controller Technical Bulletin